Technical Specifications
Technical Characteristics
Input Parameters
Frequency Range
40Hz ~ 70 Hz
Phase
Single phase with ground
Power Factor
≥ 0.99 @ 220 to 230 VAC (input voltage)
Voltage Range
Low Line Transfer
160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 %( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback
175 VAC ± 5 %
High Line Transfer
300 VAC ± 5 %
High Line Comeback
290 VAC ± 5 %
Output Parameters
Output Voltage
208/220/230/240VAC
AC Voltage Regulation
± 3% (Batt. Mode)
47 to 53 Hz or 57 to 63 Hz (Synchronized Range)
Frequency Range (Batt. Mode)
50 Hz ± 0.25Hz
Overload
100% to 110%: audible warning110% to 130%: UPS shuts down in 30 seconds at battery mode or transfers to bypass mode when the utility is normal.>130%: UPS shuts down immediately at battery mode or transfer to bypass mode when the utility is normal.
Current Crest Ratio
3:1
Harmonic Distortion
≤ 3 % THD (Linear Load)≤ 4 % THD (Linear Load)
≤ 6 % THD (Non-linear Load)≤ 7 % THD (Non-linear Load)
Waveform (Batt. Mode)
Pure Sinewave
Efficiency
AC Mode
~ 85%
~ 88%
Battery Mode
~ 83%
Transfer Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
4 ms (Typical)
Battery Charger (Standard Model)
Battery Type
12 V / 7 AH
12 V /7 AH
12 V / 9 AH
Numbers
3
6
Typical Recharge Time
4 hours recover to 90% capacity (Typical)
Charging Current
1.0 A(max.)
Charging Voltage
41.0 VDC ± 1%
82.1 VDC ±1%
Battery Charger (Long back-up Model)
8
4.0 A or 8.0 A(max.)
109.6 VDC ±1%
Physical Parameters
Dimension, D X W X H
220 x 145 x 397
318 x 190 x 421
Net Weight (kgs)
13
7
26
28
Emvironmental Parameters
Operation Humidity
20 to 90 % RH @ 0 to 40°C (non-condensing)
Noise Level
Less than 55dBA @ 1 Meter
Management
Smart RS-232 or USB
Supports Windows 98/2000/2003/XP/Vista/2008/ 7, Linux, and MAC
Optional SNMP
Power management from SNMP manager and web browser